Model CD74TRP-E is an inferential, single stream, straight reading type meter for cold water, and it’s suitable for domestic use. The sealed register mechanism, which is filled with special liquid, is equipped with a suitable pressure compensating device. Brass body and adopt all antiseptic material, no leak. It has all the advantages which the wet or dry dial water meters possess. 
  
WORKING CONDITION: 
*The max. admissible water pressure:1.6MPa(16bar) 
*Water temp.:not more than 50℃ 
 Maximum permissible error: 
Between qt (included) and qs is ±2%; 
Between qmin and qt (excluded) is ±5%. 
NOTE: The technical data conform to ISO4064 standard, class B.
  
FLOW-ERROR CURVE
   
SPECIFICATION AND OVERAL DIMENSIONS
  
| 
 Description  | 
 Unit  | 
 Hydraulic data and dimensions   |  
| 
 Nominal size   | 
 mm  | 
 15  | 
 20  | 
 25  |  
| 
 inch  | 
 1/2  | 
 3/4  | 
 1  |  
| 
 Overload flow-rate (qs)  | 
 m3/h  | 
 3  | 
 5  | 
 7  |  
| 
 Permanent flow-rate (qp)  | 
 m3/h  | 
 1.5  | 
 2.5  | 
 3.5  |  
| 
 Transitional flow-rate (qt)  | 
 m3/h  | 
 0.12  | 
 0.2  | 
 0.28  |  
| 
 Minimum flow-rate (qmin)  | 
 m3/h  | 
 0.03  | 
 0.05  | 
 0.07  |  
| 
 Max. reading   | 
 m3  | 
 99999.9999  | 
 99999.9999  | 
 99999.9999  |  
| 
 Min. reading  | 
 m3  | 
 0.00005  | 
 0.00005  | 
 0.00005  |  
| 
 Max. working pressure   | 
 MPa  | 
 1.6  | 
 1.6  | 
 1.6  |  
| 
 ΔP at the qs   | 
 MPa  | 
 ≤0.1  | 
 ≤0.1  | 
 ≤0.1   |  
| 
 L  | 
 mm  | 
 110  | 
 130  | 
 160  |  
| 
 I  | 
 mm  | 
 190  | 
 230  | 
 280  |  
| 
 H  | 
 mm  | 
 89  | 
 89  | 
 89  |  
| 
 B   | 
 mm  | 
 88  | 
 88  | 
 88  |   
OVERALL DIMENSIONS                                                                            PRESSURE LOSS CURVE
    |